# Variable Frequency Drive [VFD]

> What a variable frequency drive (VFD) is, how it controls motor speed, where VFDs are used on fans and pumps in buildings, and key installation tips.

- URL: https://essential.construction/academy/glossary/variable-frequency-drive/
- Author: Kyle Parry (https://essential.construction/about-us/kyle-parry/, https://www.linkedin.com/in/kyleparry/) - Kyle Parry is the founder of Essential Construction. He has worked in construction for more than 20 years, leading projects across Canada for the country's largest contractors and developers.
- Publisher: Essential Construction (https://essential.construction/)
- Last updated: 2026-11-03

---

A variable frequency drive (VFD) is a type of motor controller that drives an electric motor by varying the frequency and voltage supplied to it. Other names for a VFD are **variable speed drive**, **adjustable speed drive**, **adjustable frequency drive**, **AC drive**, **microdrive** and **inverter**.

An AC motor's speed is tied to the frequency of its power supply. If a fan or pump does not need to run at full speed, the VFD lowers the frequency and voltage to match the load, and raises them again when demand increases.

## How a VFD works

1. **Rectifier (converter)** - diodes convert the incoming AC supply to DC. A standard drive uses six diodes, which is why it is called a six-pulse drive.
2. **DC bus** - capacitors smooth and store the DC.
3. **Inverter** - fast transistor switches (IGBTs) chop the DC into pulses using pulse width modulation, producing a simulated AC output at whatever frequency the motor needs.

Supply frequency is 60 Hz in North America and 50 Hz in the UK and Europe, but a VFD can run a motor below (and within limits above) that speed.

## Where VFDs are used in buildings

- Supply and return fans on [air handling units](https://essential.construction/academy/glossary/air-handling-unit/), especially in VAV systems
- Chilled water, heating water and condenser water pumps
- Cooling tower fans and domestic water booster pumps
- Parking garage and exhaust fans controlled by demand

## Why VFDs save energy

For centrifugal fans and pumps, the affinity laws say flow changes with speed, pressure with speed squared and power with speed cubed. In theory, running at 80% speed needs only about half the power (0.8 x 0.8 x 0.8 = 0.51). Throttling with dampers or valves wastes most of that saving. VFDs also give soft starts, cutting inrush current and mechanical wear.

## Installation and commissioning tips

- Confirm the motor is suitable for inverter duty, and consider shaft grounding where bearing currents are a risk.
- Check harmonic requirements (IEEE 519 is often specified) and whether line reactors or filters are needed.
- Follow the manufacturer's limits on motor cable length, ventilation and clearances.
- Confirm whether a bypass is specified so equipment can run if the drive fails.
- Set minimum and maximum speeds, ramp times and skip frequencies, and prove BAS control and alarm points during commissioning.

## VFD vs soft starter

A soft starter only ramps the voltage up and down at start and stop; the motor then runs at full speed. A VFD controls speed continuously, which is what delivers the energy savings.

## Related terms

- [Air Handling Unit (AHU)](https://essential.construction/academy/glossary/air-handling-unit/)
- [Fan Coil Unit (FCU)](https://essential.construction/academy/glossary/fan-coil-unit/)
- [Heat Pump](https://essential.construction/academy/glossary/heat-pump/)
- [Ductwork](https://essential.construction/academy/glossary/ductwork/)

## Related templates and guides

- [Introduction to Mechanical and Electrical Systems](https://essential.construction/academy/tutorials/introduction-to-mechanical-and-electrical-systems/)
- [Five Ways to Make Your Building More Efficient](https://essential.construction/academy/tutorials/five-ways-make-building-efficient/)
- [HVAC Design Quality Checklist](https://essential.construction/files/construction/quality/hvac-design-quality-checklist/)

## Frequently asked questions

### What is a VFD used for?

A VFD controls the speed of an AC motor to match demand. In buildings that mostly means fans and pumps in HVAC and plumbing systems, where slowing the motor saves energy, reduces noise and gives smoother control than dampers or throttling valves.

### Can a VFD create three-phase power from single-phase?

Many drives can be fed from a single-phase supply and still output three-phase power to the motor. The drive usually has to be derated, or a model built for single-phase input used. Always check the manufacturer's data before sizing one this way.

### Can a VFD be used on pumps?

Yes. Variable-speed pumping is one of the most common VFD applications, for chilled water, heating water, condenser water and domestic booster systems. The pump speed is usually controlled from a pressure or flow sensor to hold a setpoint.

### Does a VFD save energy on every motor?

No. Savings come from running below full speed. A motor that must run at full load all the time gains little and loses a small amount in the drive itself. The best candidates are fans and pumps with loads that vary through the day or season.