{"id":6837,"date":"2019-08-03T15:06:32","date_gmt":"2019-08-03T20:06:32","guid":{"rendered":"https:\/\/essential.construction\/academy\/?p=6837"},"modified":"2026-11-03T12:38:46","modified_gmt":"2026-11-03T19:38:46","slug":"firestopping-in-construction-and-buildings","status":"publish","type":"post","link":"https:\/\/essential.construction\/academy\/tutorials\/firestopping-in-construction-and-buildings\/","title":{"rendered":"Firestopping In Construction and Buildings"},"content":{"rendered":"\n<p class=\"wp-block-paragraph\"><strong>Firestopping is the use of tested, fire-resistant materials to seal the openings and joints in fire-rated walls and floors<\/strong>, such as the gaps around pipes, cables and ducts, and the joints at the head of a wall or the edge of a slab. It keeps fire and smoke from passing through those gaps, so the wall or floor still delivers the fire rating it was designed for.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">On one of the first projects I worked on, the architect asked us if the firestopping material was installed in the movie theatre. Because I was new, I had no idea what this crucial part of the building&#8217;s life safety systems was. So what exactly is firestopping and how is it used in construction?<\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><strong>Through my investigation I discovered that firestopping can be a range of materials that are installed in joints within walls, ceilings and floors that have a fire rating to slow the spread of fire throughout a structure. <\/strong><\/p>\n\n\n\n<p class=\"wp-block-paragraph\">There are many different forms of firestopping so let&#8217;s jump right in and review where it is found, types of materials, how it&#8217;s detailed and what it actually does.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Where Can I Find Firestopping In A Building?<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Firestopping can be found within a building at many different locations. Some of the most common locations where firestopping can be found include:<\/p>\n\n\n\n<ul class=\"wp-block-list\"><li>Horizontal gaps between floors (ie at expansion joints)<\/li><li>Penetrations in fire rated walls where services run through<\/li><li>Around door frames<\/li><li>Tops and bottoms of fire rated walls<\/li><li>Joints in fire rated shaft walls<\/li><li>The perimeter gap between the slab edge and a curtain wall (a perimeter fire barrier)<\/li><li>Penetrations through fire rated floor slabs, such as risers, sleeves and floor drains<\/li><\/ul>\n\n\n\n<p class=\"wp-block-paragraph\">These are just a few of the examples of where it can be found. The important thing to remember is that any time there is a room that requires a fire rating firestopping is most likely present to seal any of the cracks and openings going in and out of the room.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">How Can I Identify Where It&#8217;s Required?<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">An easy way to identify where firestopping needs to be applied in a building is to review the fire separation plans. Don&#8217;t know what a fire separation plan is?<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">A fire separation plan is typically prepared by the architect and defines, based on the building code, where fire rated walls occur. It identifies the separation and the required rating by highlighting them on a floor plan.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">By reviewing which partitions have fire ratings you can easily determine which walls and slabs require firestopping to ensure the continuation of the fire rating.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">What Does Firestopping Do?<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\"><strong>Firestopping is considered a form of passive fire protection in a building. Its intention is to help slow the spread of fire throughout a building by containing it within a room. <\/strong>But what exactly does that mean and how is it done?<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">In North America, firestop systems are tested and listed by laboratories such as UL (USA) and ULC (Canada). Products going into the assembly need to be designed together (ie insulation and sealant material) and must be tested together as a system to provide the rating. Because materials melt at different levels it&#8217;s important that they be selected and designed to survive in high temperatures.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Many everyday building materials, such as plastic pipe, foam insulation and ordinary sealants, soften, melt or burn away at temperatures well below those reached in a building fire, leaving an open path for flame and smoke. Firestop materials are chosen and tested to hold the opening closed under those conditions. The <a href=\"https:\/\/www.fcia.org\/RESOURCES\/Presentations\" rel=\"noopener\">Firestop Contractors International Association (FCIA)<\/a> publishes free presentations if you want to go deeper.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Firestopping vs Fireblocking vs Fireproofing<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">These three terms get mixed up on site and in specifications, but they are different scopes of work:<\/p>\n\n\n\n<figure class=\"wp-block-table\"><table><thead><tr><th>Term<\/th><th>What it does<\/th><th>Where you find it<\/th><\/tr><\/thead><tbody><tr><td>Firestopping<\/td><td>Seals penetrations and joints in fire-resistance-rated walls and floors using a tested, listed system<\/td><td>Pipe, cable and duct penetrations, head-of-wall joints, slab edges and shaft walls<\/td><\/tr><tr><td>Fireblocking<\/td><td>Uses approved materials to block concealed draft openings so fire cannot race through hidden cavities in combustible (usually wood-framed) construction<\/td><td>Stud cavities at floor and ceiling levels, soffits, stair stringers and around vents in wood framing<\/td><\/tr><tr><td>Fireproofing<\/td><td>Protects the structural frame itself (usually steel) so it keeps its strength in a fire<\/td><td>Spray-applied fireproofing, intumescent paint and board encasement on beams and columns<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<p class=\"wp-block-paragraph\">The key test: firestopping is triggered when something penetrates or joins an assembly that has a required hourly fire-resistance rating. Fireblocking applies to concealed spaces in combustible construction whether or not the assembly is rated, and it is not a substitute for a listed firestop system. For more on protecting the structure, see our guide to <a href=\"https:\/\/essential.construction\/academy\/tutorials\/fireproofing-safeguarding-your-building\/\">fireproofing<\/a>.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Materials Typically Used in Firestopping Systems<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Firestopping assemblies have been designed by companies throughout the world. Some of them are special products others are a combination of products to make up an assembly.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><strong>One of the most common types of firestopping assemblies involves installing mineral wool rated insulation in the cavity space to stop the spread of fire and installing a smoke seal on both sides of the separation.<\/strong> Stone (mineral) wool used for firestopping has a melting point above 1,000\u00b0C (over 1,800\u00b0F), far higher than plastics and ordinary sealants. By applying the smoke seal to both sides of the penetration you ensure it is always intact on the side of the wall away from the fire.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Many companies that provide firestopping materials will do designs with their products for you and provide visual guides on installation that will comply with their designs. As an example &#8211; <a href=\"https:\/\/www.usg.com\/content\/dam\/USG_Marketing_Communications\/united_states\/product_promotional_materials\/finished_assets\/firestopping-construction-joints-and-penetration-systems-catalog-en-usa-SA727.pdf\" rel=\"noopener\">USG one of the major drywall suppliers provides a catalog which includes details<\/a> on  how to seal pipe penetrations, tops and bottoms of walls and many other common construction situations. While this isn&#8217;t a requirement it is designed to help teams simplify their on site work.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Other examples of firestopping include more modular products that are engineered and designed to be installed in certain situations without the need for complicated installs. <\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><strong>Expansion Joints &#8211; <\/strong>rated expansion joints that are prefabricated exist on the market. Rather than require complicated insulation and smoke seal these are rubber assemblies that are simply installed in a joint.<a href=\"https:\/\/www.amazon.com\/gp\/product\/B00X44865A\/ref=as_li_tl?ie=UTF8&amp;camp=1789&amp;creative=9325&amp;creativeASIN=B00X44865A&amp;linkCode=as2&amp;tag=cnstrctr0f-20&amp;linkId=a6b23edb18d1a955db18c89722d16853\" rel=\"noopener\"> As an example Emseal offers these.<\/a><\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><strong>Cable Penetrations<\/strong> &#8211; rather than install a custom joint around cables or pipes vendors have started providing manufactured products that can be installed on partitions to provide an equivalent rating. While these products are typically much more expensive they do provide an ease of installation and cleanliness. <a href=\"https:\/\/www.amazon.com\/gp\/product\/B01MTJSM9N\/ref=as_li_tl?ie=UTF8&amp;camp=1789&amp;creative=9325&amp;creativeASIN=B01MTJSM9N&amp;linkCode=as2&amp;tag=cnstrctr0f-20&amp;linkId=9593e55344cfcebbdf2a166e6d4cd81a\" rel=\"noopener\">Hilti has many different cable penetrations available.<\/a><\/p>\n\n\n\n<p class=\"wp-block-paragraph\">These are just two examples, there are hundreds of products available on the market for many different applications. A simple google search or asking an industry professional will help you to discover them.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">What Materials Is Firestopping Made Of?<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\"><strong>Firestopping is typically made up of materials that have a strong fire resistance and burn slowly (or not at all). Firestopping is typically made up of cement based products, intumescent containing products, putties (for binding), non combustible fibres, and rubber compounds.<\/strong><\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Firestopping Standards and Ratings: F, T and L Ratings Explained<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">A firestop system is only as good as the test it passed. Before you approve a submittal or sign off an install, check that the system was tested to the standard your building code calls for and that the rating matches the wall or floor being penetrated.<\/p>\n\n\n\n<figure class=\"wp-block-table\"><table><thead><tr><th>Region<\/th><th>Penetrations<\/th><th>Joints and perimeter gaps<\/th><th>Code reference<\/th><\/tr><\/thead><tbody><tr><td>USA<\/td><td>ASTM E814 or UL 1479 (F, T and L ratings)<\/td><td>ASTM E1966 or UL 2079 for joint systems; ASTM E2307 for perimeter fire barriers at curtain walls<\/td><td>International Building Code (IBC) Chapter 7 &ndash; Section 714 covers penetrations<\/td><\/tr><tr><td>Canada<\/td><td>CAN\/ULC-S115 (F, FT, FH and FTH ratings)<\/td><td>CAN\/ULC-S115<\/td><td>National Building Code of Canada and provincial codes<\/td><\/tr><tr><td>UK and Europe<\/td><td>BS EN 1366-3, classified to BS EN 13501-2<\/td><td>BS EN 1366-4 for linear joint seals, classified to BS EN 13501-2<\/td><td>Approved Document B (England) and the national regulations elsewhere<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<p class=\"wp-block-paragraph\"><strong>F rating<\/strong> &ndash; how long (in hours) the system stops flame passing through the opening. <strong>T rating<\/strong> &ndash; how long it also limits the temperature rise on the non-fire side, so combustibles touching the penetration do not ignite. <strong>L rating<\/strong> &ndash; how much air (smoke) leaks through the system, which matters in smoke barriers. In the IBC, penetrations through rated walls generally need an F rating at least equal to the wall rating, and penetrations through rated floors generally need both F and T ratings, with some exceptions.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">In the UK, third-party certification of both products and installers is widely used to show compliance. Look for firestopping products with independent certification and installers working under a recognised third-party scheme.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">How Firestopping Is Installed: Step by Step<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Every listed system comes with its own drawing and limits, so always work from the system detail. The general sequence on site looks like this:<\/p>\n\n\n\n<ol class=\"wp-block-list\">\n<li><strong>Confirm the rating.<\/strong> Check the fire separation plans for the rating of the wall or floor being penetrated.<\/li>\n\n\n\n<li><strong>Pick the listed system.<\/strong> Match the system to the assembly type (concrete floor, gypsum wall and so on), the penetrating item (material and diameter of pipe, cable bundle, duct, insulated or not) and the annular space. If no listed system fits, request an engineering judgement before the work starts.<\/li>\n\n\n\n<li><strong>Submit it.<\/strong> Send the system details to the design team for review as part of your <a href=\"https:\/\/essential.construction\/academy\/tutorials\/managing-construction-submittals\/\">construction submittals<\/a>.<\/li>\n\n\n\n<li><strong>Prepare the opening.<\/strong> The opening must be clean, dry and sized within the limits of the system. Fix any oversized holes before sealing.<\/li>\n\n\n\n<li><strong>Install packing or backing.<\/strong> Pack mineral wool or the specified backer to the depth shown on the system detail.<\/li>\n\n\n\n<li><strong>Apply the firestop product.<\/strong> Install the sealant, mortar, collar, wrap or device to the specified depth and on the specified sides of the assembly.<\/li>\n\n\n\n<li><strong>Label and record.<\/strong> Label the penetration where required, and photograph it with the system number before it is covered.<\/li>\n\n\n\n<li><strong>Inspect before closing up.<\/strong> Get the work inspected before ceilings or wall finishes hide it.<\/li>\n<\/ol>\n\n\n\n<h2 class=\"wp-block-heading\">Inspection Requirements for Firestopping<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Because firestopping is part of the fire protection system within the building, it&#8217;s important that the system be inspected before the work is completed and\/or covered up.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">The first step in the process is that the location of all joints is defined and designed by Local, State and National building codes. Other associations such as the NFPA (National Fire Protection Association) also have guidelines with respect to the design of assemblies.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Once that&#8217;s been completed it&#8217;s important to select products which are designed in accordance with industry standards. In North America, the products must be part of a system tested and listed to the UL or ULC standards your code references. Each product must be tested to ensure conformance. Prior to application you need to ensure that your products aren&#8217;t expired.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">As noted above, assemblies are designed by manufacturers and tested and listed by laboratories such as UL and ULC. That being said you may run into instances where a typical design just doesn&#8217;t work. I had this occur on a past project &#8211; the expansion joint was an atypical design. When this occurs you may need to engage an engineer to prepare an engineering judgement for you.<\/p>\n\n\n\n<h4 class=\"wp-block-heading\">What is an engineering judgement?<\/h4>\n\n\n\n<p class=\"wp-block-paragraph\"><strong>Through my project experience I have required a number of these. An engineering judgement is where a typical assembly design does not exist. Because your specific application is unique an engineer will review existing assemblies and materials and prepare a detail or proposal for you that meets the code requirements of your site specific design. <\/strong><\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Because an engineering judgement is unique to your project the building department may want a copy. Ensure that you keep a copy readily available.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Once you&#8217;ve completed the work, you&#8217;ll need to ensure your local building inspector is reviewing the firestopping application. If the work is behind drywall you&#8217;ll want to bring them in before you close the wall. If the application is out in the open you can bring them in at a regular interval to inspect the work prior to turnover of the building.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">On larger projects in the US, the IBC also requires special inspection of penetration firestops and fire-resistant joint systems by an approved agency in high-rise buildings and buildings assigned to Risk Category III or IV. Those inspections follow ASTM E2174 (penetrations) and ASTM E2393 (joints), so plan the inspection agency into your schedule early.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Besides the building inspector, you may want to bring in a manufacturer representative to ensure that the application is in conformance with their details. This ensures that in the event of an incident and \/ or product failure the applicator cannot be blamed.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Common Firestopping Mistakes<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Most firestopping failures found at inspection come down to a handful of repeat problems:<\/p>\n\n\n\n<ul class=\"wp-block-list\">\n<li>Using a product from one manufacturer with a system listed by another, or mixing products within one system.<\/li>\n\n\n\n<li>Sealing a penetration that does not match the listed system (wrong pipe material, too large a pipe, or too wide an annular space).<\/li>\n\n\n\n<li>Installing sealant to less than the depth shown on the system drawing, or on one side only when both sides are required.<\/li>\n\n\n\n<li>Using expanding foam or ordinary caulk that is not part of a listed firestop system.<\/li>\n\n\n\n<li>Trades adding new cables or pipes through a sealed opening after it has been inspected.<\/li>\n\n\n\n<li>Covering the work before it has been inspected and photographed.<\/li>\n<\/ul>\n\n\n\n<h2 class=\"wp-block-heading\">Tips for Contractors and For Firestopping<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">There are a few general tips for contractors looking to ensure that the firestopping scope of work is covered in their project:<\/p>\n\n\n\n<ul class=\"wp-block-list\"><li>When awarding scopes of work include firestopping through walls and slabs within the trades scope of work. For example the plumber should be responsible for their own firestopping and smoke seal.<\/li><li>Keep an allowance aside for miscellaneous firestopping. There will be details missed on any project where it is required and not noted on the drawings. It&#8217;s best to keep a small allowance to deal with these issues.<\/li><li>Engage a known contractor &#8211; finding a contractor that is quick and provides a quality service is like finding gold. When you find one ensure you keep them in your rolodex and utilize them on your projects. <\/li><li>Make the review of firestopping something that is done at an early stage in the project. This way you don&#8217;t end up closing a wall early and have costly re-work to add it after the fact.<\/li><li>Keep a catalogue of typical firestopping details from your chosen manufacturer (for example CGC or USG) on hand and check trades work regularly to ensure they are complying with the standard details.<\/li><li>Bring your building inspector in at regular intervals and have them review the work. This gives them a better comfort that you know what you&#8217;re doing and can help to identify major concerns early.<\/li><li><strong><a href=\"https:\/\/essential.construction\/academy\/tutorials\/learning-how-to-caulk\/\">If you&#8217;re interested in how to install firestopping, we have a great video for you to watch in one of our other articles.<\/a><\/strong><\/li><\/ul>\n\n\n\n<p class=\"wp-block-paragraph\">There are many other great pieces of advice regarding this scope of work. But the most important is really just to pay attention to the details for firestopping and don&#8217;t overlook it.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Wrapping Up (Literally)<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Firestopping is a critical part of any project and requires attention to ensure it is both captured within a trades scope and installed properly in the correct locations. Make sure that you pay attention to the firestopping details on your next construction project!<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">How has firestopping been applied on your projects? Let us know below in the comments and include any lessons learned.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Firestopping FAQ<\/h2>\n\n\n\n<h3 class=\"wp-block-heading\">What is firestopping in construction?<\/h3>\n\n\n\n<p class=\"wp-block-paragraph\">Firestopping is the sealing of openings and joints in fire-resistance-rated walls and floors with a tested, listed system, so fire and smoke cannot pass through where pipes, cables, ducts or construction joints break the assembly.<\/p>\n\n\n\n<h3 class=\"wp-block-heading\">What materials are used for firestopping?<\/h3>\n\n\n\n<p class=\"wp-block-paragraph\">Common firestop materials include intumescent sealants, collars and wraps, mineral (stone) wool packing, cement-based mortars, firestop putty and pillows, silicone and acrylic sealants, and prefabricated devices for cables and pipes. They only provide a rating when installed as part of a tested system.<\/p>\n\n\n\n<h3 class=\"wp-block-heading\">What is the difference between firestopping and fireblocking?<\/h3>\n\n\n\n<p class=\"wp-block-paragraph\">Firestopping seals penetrations and joints in fire-rated assemblies using listed systems. Fireblocking closes concealed spaces in combustible construction, such as stud cavities, to slow fire spread through hidden voids. Fireblocking materials are not a substitute for a listed firestop system.<\/p>\n\n\n\n<h3 class=\"wp-block-heading\">What is the British standard for fire stopping?<\/h3>\n\n\n\n<p class=\"wp-block-paragraph\">In the UK, penetration seals are tested to BS EN 1366-3 and linear joint seals to BS EN 1366-4, with results classified to BS EN 13501-2. Approved Document B sets the performance expectations in England, and third-party certification is widely used to show compliance.<\/p>\n\n\n\n<h3 class=\"wp-block-heading\">Who is responsible for firestopping on a construction project?<\/h3>\n\n\n\n<p class=\"wp-block-paragraph\">It depends on the contract. Many general contractors make each trade responsible for firestopping its own penetrations, while others hire a single specialist firestop contractor. Either way, the scope should be written clearly into the subcontracts so nothing falls between trades.<\/p>\n\n\n\n<h3 class=\"wp-block-heading\">Does firestopping need to be inspected?<\/h3>\n\n\n\n<p class=\"wp-block-paragraph\">Yes. Firestopping should be inspected before it is covered up. Many jurisdictions require the building inspector to see it, and in the US the IBC requires special inspection by an approved agency on high-rise and Risk Category III and IV buildings.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Related Templates and Guides<\/h2>\n\n\n\n<ul class=\"wp-block-list\">\n<li><a href=\"https:\/\/essential.construction\/files\/information\/guides\/firestopping-101-introduction-to-firestopping\/\">Firestopping 101 &ndash; Introduction to Firestopping<\/a><\/li>\n\n\n\n<li><a href=\"https:\/\/essential.construction\/files\/information\/guides\/firestop-inspection-manual-handbook\/\">Firestopping Inspection Manual Handbook<\/a><\/li>\n\n\n\n<li><a href=\"https:\/\/essential.construction\/files\/design\/autocad\/general-details-and-notes-fire-protection\/\">General Details and Notes &ndash; Fire Protection (AutoCAD)<\/a><\/li>\n<\/ul>\n\n","protected":false},"excerpt":{"rendered":"<p>Keep Your Building Fire Safe<\/p>\n","protected":false},"author":1,"featured_media":11597,"comment_status":"open","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[3,27,99,31,19],"tags":[598,286,597,596,595,599],"class_list":["post-6837","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-all-posts","category-division-01-general-requirements","category-division-07-thermal-and-moisture-protection","category-featured-articles","category-general-construction-knowledge","tag-caulking","tag-contractor-1","tag-fire-block","tag-firestop","tag-firestopping","tag-smoke-seal","generate-columns","tablet-grid-50","mobile-grid-100","grid-parent","grid-33"],"_links":{"self":[{"href":"https:\/\/essential.construction\/academy\/wp-json\/wp\/v2\/posts\/6837","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/essential.construction\/academy\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/essential.construction\/academy\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/essential.construction\/academy\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/essential.construction\/academy\/wp-json\/wp\/v2\/comments?post=6837"}],"version-history":[{"count":1,"href":"https:\/\/essential.construction\/academy\/wp-json\/wp\/v2\/posts\/6837\/revisions"}],"predecessor-version":[{"id":20397,"href":"https:\/\/essential.construction\/academy\/wp-json\/wp\/v2\/posts\/6837\/revisions\/20397"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/essential.construction\/academy\/wp-json\/wp\/v2\/media\/11597"}],"wp:attachment":[{"href":"https:\/\/essential.construction\/academy\/wp-json\/wp\/v2\/media?parent=6837"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/essential.construction\/academy\/wp-json\/wp\/v2\/categories?post=6837"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/essential.construction\/academy\/wp-json\/wp\/v2\/tags?post=6837"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}